HEAVY WELDED CONNECTORS

Wood To Concrete Truss Hangers NVFSU

Concrete Strength Allowable loads
Carried Truss 1 Ply NVFSU1A 2 Ply NVFSU2A 3 Ply NVFSU3A 4 Ply NVFSU4A 5 Ply NVFSU5A
2000 Gravity & Uplift 4015 4015 7170 8030 8030
2500 Gravity & Uplift 4075 4075 7275 8150 8150
3000 Gravity & Uplift 4135 4135 7380 8270 8270


Structural Notes: Wood to Concrete
1) All design conforms to 2004 FBC and 2003 IBC and IRC and NDS 2001.
2) 1/4" thick structural steel shall conform to ASTM A36, yield strength 36000 psi. All bolt holes are 13/16" diameter.
3) All welding shall be minimum 3/16" with E70 electrodes and shall conform to latest AISC/AWS codes. All welds shall be fillet welds.
4) All bolt values in wood conform to NDS 2001 for Southern Pine, G=0.55. Values for other
species shall be adjusted as per NDS 2001. Bolts are 3/4" diameter.
5) Bolts shall not penetrate Truss Top and bottom chords and shall only be through Truss Verticals.
Bolts thru wood shall conform to section 11.1.2 of NDS 2001 and table 11G for shear values.
6) This connector shall only be used for wood members loaded parallel to grain.
7) Steel stress is not increased by 33%.
8) Provide plywood shims to close the gap between carried members and steel connectors to prevent bending of bolts.
9) All Power Fasteners wedge bolt anchors shall be per Miami-Dade NOA #00-0229.04 issued May 1, 2003. Minimum anchor embedment shall be 6". Anchor diameter is 3/4". Bolt values are without 33% increase.
10) Uplift values shown are reduced for bolt spacing and edge distance per NOA #00-0229.04. Uplift values shall not exceed Truss chord capacity.
11) All products are painted Royal Blue for easy identification.