HEAVY WELDED CONNECTORS

Wood to Wood Truss Hangers NVFHE

Carried
Truss
Verticals
Allowable Lateral Loads (lbs.)
Carried
Truss
12" High
16" High
1 Ply
NVFHE1C
2 Ply
NVFHE2C
3 Ply
NVFHE3C
4 & 5 Ply
NVFHE4C, 5C
1 Ply
NVFHE1D
2 Ply
NVFHE2D
3 Ply
NVFHE3D
4 & 5 Ply
NVFHE4D, 5D
1PLY
1 - 2x6
L1
510
865
1135
1730
765
1300
1700
2595
L2
890
1790
2390
2690
1330
2680
3580
4030
2 PLY
2 - 2X6

L1
870
1340
1905
2675
1310
2010
2860
4015
L2
890
1790
2390
2690
1330
2680
3580
4030
3 PLY
3 - 2X8

L1
1055
1546
2295
3095
1585
2320
3440
4640
L2
890
1790
2390
2690
1330
2680
3580
4030
4 & 5 PLY
4 - 2X8
5 - 2X8

L1
1136
1632
1866
3265
1705
2450
3690
4895
L2
890
1790
2390
2690
1330
2680
3580
4030
NVFHE1C, NVFHE2C, NVFHE3C, NVFHE4C & NVFHE5C-12" High
NVFHE1D, NVFHE2D, NVFHE3D, NVFHE4D & NVFHE5D-16" High




Weld A: 8" long for 12" high & 10" long for 16" high plates and 1/2" at top.
Weld B: Continouous 3/16" Fillet.
Weld C: Continuous 3/16" Fillet.

Plates a: 4" x 1/4"x 12" or 16"
Plate b: (X+1/2") x 1/4" x 12" or 16"
Plate c: (X+1/2") x 1/4" x 4 1/4"

NVFHE
Carried Truss Veritcals
1C, 1D
2 X 4
2C, 2D
2 X 6
3C, 3D
2 X 8
4C, 4D
2 X 8
5C, 5D
2 X 8

Structural Notes: Wood to concrete and wood to wood connectors.

1) All design conforms to 2004 FBC and 2003 IBC and IRC AND NDS 2001.
2) 1/4" thick Structural steel shall conform to ASTM A36, yield strength 36000 psi. All bolt holes are 13/16" diameter.
3) All welding shall be minimum 3/16" with E70 electrodes and shall conform to latest AISC/AWS codes. All welds shall be fillet welds.
4) All Power Fasteners wedge bolt anchors shall be per Miami-Dade NOA #00-0209.04 issued May 1, 2003. Minimum anchor diameter is 3/4" and anchor embedment shall be 6".
5) Lateral values in concrete shown are reduced for bolt spacing and edge distance per NOA #00-0209.4. Power fasteners are used without 33% increase in allowable values.
6) All bolt values in wood conform to NDS 2001 for southern pine, G=0.55. Values for other species shall be adjusted as per NDS 2001. Bolts are 3/4" diameter.
7) Bolts shall not penetrate Truss top and bottom chords and shall only be through Truss Verticals. Bolts thru wood shall conform to section 11.1.2 of NDS 2001 and table 11 G for shear values.
8) This connector shall only be used for wood members loaded parallel to grain.
9) Steel stress is not increased by 33%.
10) Provide plywood shims to close the gap between truss chords to obtain full bearing and prevent bending of thru bolts.
11) Lateral loads shall be combined with uplift loads to satisfy the equation:
   Actual Uplift   
Allowable Uplift
+    Actual L1   
Allowable L1
+    Actual L2   
Allowable L2
<=    1.0
12) All products are painted Royal Blue for easy identification